Default Call for heat no boiler fire???

I have a three zone very basic boiler system in my home. Two upstairs zones in one's own in the basement. The basement heating zone works perfect. I turn up the thermostat, moments later the boiler fires and all is well. The two upstairs zones are the issue. Whenever I turn either of them up calling for heat the zone valve opens but that is it. The sequence of operation stops there. The boiler never fires. I have the old antiquated tstats as pictured. The boiler also makes our hot domestic hot water and that zone too works perfect. I am hoping it is just a thermostats that need to be replaced. What would cause the zone valve to open up but not continue the firing sequence!? I am a master plumber but by no means a service guy. I run larger commercial projects. Can someone please give me some insight!!!?? I'd surely appreciate any and all help/advice!!
Attached Thumbnails
Call for heat no boiler fire???-img_20181009_153619819_1539121659128.jpg  

Jklsr55 is offline   Reply With Quote

Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. PlumbingZone.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 10-09-2018, 07:38 PM   #2
Senior Member
 
ShtRnsdownhill's Avatar
 
Join Date: Jan 2016
Location: Long Island, NY
Posts: 6,180

View ShtRnsdownhill's Photo Album My Photos
Default

the end switches in the zone valve are corroded, pull the motor and that black micro switch is the issue , spray some anti corrosion spray in it, or take them out and open them up to spray, if no worky replace them, this is for honeywell zone valves..nothing todo with thermostats..
__________________
You cant cure stupid, only kill it..
ShtRnsdownhill is offline   Reply With Quote
Old 10-10-2018, 11:35 AM   #3
The Old (antique) Master
 
PLUMBER_BILL's Avatar
 
Join Date: Oct 2009
Location: ALLENTOWN, PA
Posts: 2,246

View PLUMBER_BILL's Photo Album My Photos
Default

[QUOTE=Jklsr55;1186348]I have a three zone very basic boiler system in my home. Two upstairs zones in one's own in the basement.
The basement heating zone works perfect. I turn up the thermostat, moments later the boiler fires and all is well. The two upstairs zones are the issue. Whenever I turn either of them up calling for heat the zone valve opens but that is it. The sequence of operation stops there.


Lets think outside the box. What if the 2nd floor was airlocked and the boiler was satisfied and a call for heat came in. There would be no circulation so the boiler temp would not drop and the boiler would not start. Did you have noise in the system before this happened?
I am assuming that your radition is non-ferrous baseboard.
skoronesa likes this.
__________________
Bill Parr LMP
www.parrsplumbing.net
For my alternate web site, click on ...
A little of this and a little of that
PLUMBER_BILL is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 10-10-2018, 07:16 PM   #4
Junior Member
 
Join Date: Apr 2013
Location: Connecticut
Posts: 20

View jtmell's Photo Album My Photos
Default

The Thermostat should open the zone valve and turn on the circulator.If the circulator works I would also think the top floors are airbound.
skoronesa likes this.
jtmell is offline   Reply With Quote
Old 10-15-2018, 06:50 PM   #5
Member
 
Join Date: Jun 2010
Posts: 59

View Turd Herder's Photo Album My Photos
Default

Ok Mr. "Master Plumber",
What you need to check for is continuity on the end switch (wires) at the boiler or off the zone valve or zone valve controller. . Do you have zone valves in your system or do you have zone pumps? Likely a picture of your boiler system will help us help you more than a pic of your thermostats.

Most likely, as some one stated above, one of your zone valves is not closing the end switch.

Post that picture!
Turd Herder is offline   Reply With Quote
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Added Indirect Tank to Boiler Loop Need Help! ocyrus411 Boilers, Hot Water & Steam Heating 5 06-28-2018 02:21 AM
Hybrid Boiler System - Relief Valve Question GRC Boilers, Hot Water & Steam Heating 7 10-07-2017 08:38 AM
Help with HB Smith HSI boiler. plumbcrazy81 Boilers, Hot Water & Steam Heating 1 02-29-2016 07:24 PM
Low water cut off - why you need one nhmaster3015 Boilers, Hot Water & Steam Heating 13 08-21-2015 11:59 PM


All times are GMT -4. The time now is 05:13 PM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2020, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | ElectricianTalk.com | HVACSite.com | PaintTalk.com | RoofingTalk.com