Default air elimination from five story building

air elimination from five story building... How would you start to fill and purge air from the heating system. each floor can be isolated... Any suggestions?
Jklsr55 is offline   Reply With Quote

Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. PlumbingZone.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Old 09-30-2010, 06:28 AM   #2
Registered User
 
SlickRick's Avatar
 
Join Date: Sep 2009
Location: Gilmer, Texas
Posts: 8,090

View SlickRick's Photo Album My Photos
Default

Hello! Introduction Requested
An intro is requested from all new members. In case you missed it, here is the link. http://www.plumbingzone.com/f3/.

The PZ is for Plumbing Professionals ( those engaged in the plumbing profession)

Post an intro and tell our members where you are from, yrs in the trade, and your area(s) of expertise in the plumbing field.

This info helps members who are waiting to welcome you to the best plumbing site there is.

We look forward to your valuable input.
SlickRick is offline   Reply With Quote
Old 09-30-2010, 06:59 AM   #3
I Like Tater Tots
 
Pipe Rat's Avatar
 
Join Date: Apr 2009
Location: St. Louis, Mo.
Posts: 1,185

View Pipe Rat's Photo Album My Photos
Default

Me kinda thinks if you're lost already at the filling and purging stage you have no business at all working on this system.
Pipe Rat is offline   Reply With Quote
The Following User Says Thank You to Pipe Rat For This Useful Post:
futz (10-01-2010)
Old 09-30-2010, 07:08 AM   #4
Registered User
 
SlickRick's Avatar
 
Join Date: Sep 2009
Location: Gilmer, Texas
Posts: 8,090

View SlickRick's Photo Album My Photos
Default

Water treatment will be the next question.

Google your way to being a mech supt. 101.

Last edited by SlickRick; 09-30-2010 at 07:11 AM..
SlickRick is offline   Reply With Quote
Old 09-30-2010, 07:18 AM   #5
Senior Member
 
RealLivePlumber's Avatar
 
Join Date: Jun 2008
Location: NJ
Posts: 3,067

View RealLivePlumber's Photo Album My Photos
Default

Quote:
Originally Posted by Jklsr55 View Post
air elimination from five story building... How would you start to fill and purge air from the heating system. each floor can be isolated... Any suggestions?
I'd start by turning the water on......
__________________
RealLivePlumber
You can make it happen, you can watch it happen, or you can wonder wtf happened.
Phil Harris 2009
RealLivePlumber is offline   Reply With Quote
The Following 2 Users Say Thank You to RealLivePlumber For This Useful Post:
Airgap (09-30-2010), Shuanvon (10-13-2010)
Old 09-30-2010, 11:57 AM   #6
Moderator
 
Tommy plumber's Avatar
 
Join Date: Feb 2010
Location: Florida
Posts: 8,912

View Tommy plumber's Photo Album My Photos
Default

You might have to remove all the radiators to get the air out. Or if there are no radiators, purge air from slant fin baseboards.
__________________
Hire a licensed master plumber.
Tommy plumber is offline   Reply With Quote
Old 11-07-2010, 09:56 PM   #7
Master Plumber
 
Join Date: Nov 2010
Posts: 30

View accobra88's Photo Album My Photos
Default

You need airvents at the tops of the risers ...
accobra88 is offline   Reply With Quote
Old 11-07-2010, 10:24 PM   #8
WILLPLUMB4$
 
ASUPERTECH's Avatar
 
Join Date: Jun 2008
Location: Tampabay, Fl
Posts: 582

View ASUPERTECH's Photo Album My Photos
Default

Quote:
Originally Posted by Jklsr55 View Post
air elimination from five story building... How would you start to fill and purge air from the heating system. each floor can be isolated... Any suggestions?

Drill tiny holes randomly throughout the system this should allow the air to bleed off as the system is filled.. Don't forget that if you use hot water as appossed to cold that it will take less as everyone knows hot water has almost twice the volume as cold!!
__________________
$Will$
ASUPERTECH is offline   Reply With Quote
Old 11-07-2010, 10:32 PM   #9
AKA house plumber
 
Optimus Primer's Avatar
 
Join Date: May 2009
Location: New Port Richey,Fl
Posts: 3,482

View Optimus Primer's Photo Album My Photos
Default

you can drill tiny holes or using piercing saddle valves and run 1/4 cpvc out the nearest window.


Quote:
Originally Posted by ASUPERTECH View Post
Drill tiny holes randomly throughout the system this should allow the air to bleed off as the system is filled.. Don't forget that if you use hot water as appossed to cold that it will take less as everyone knows hot water has almost twice the volume as cold!!

Last edited by Optimus Primer; 11-09-2010 at 02:34 AM.. Reason: spelling
Optimus Primer is offline   Reply With Quote
The Following User Says Thank You to Optimus Primer For This Useful Post:
Redwood (11-07-2010)
Old 11-08-2010, 08:09 PM   #10
Master Plumber
 
Join Date: Nov 2010
Posts: 30

View accobra88's Photo Album My Photos
Default

" Drill tiny holes randomly throughout the system this should allow the air to bleed off"

" you can drill tiny holes or using peircing saddle valves and run 1/4 cpvc out the nearest window."

You guys are not serious about these reply's ? Your joking right ?

this is my responce also " If your asking this question you have no business working on this system"

Check carefully for the tops of the risers there should be automatic airvents installed. Turn the auto feed on and wait then turn the pump on to circulate the air eliminator should take the air out.... IF THE SYSTEM WAS INSTALLED CORRECTLY FROM THE START.

Ron



accobra88 is offline   Reply With Quote
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Ontario Building Code or National Building Code-Questions re:building drain size markb Plumbing Code 32 04-03-2012 12:55 AM
Story of Yam OldSchool Off Topic 2 06-07-2010 09:41 PM
1970s CI building drain Protech Plumbing Pictures 8 09-18-2009 02:34 PM
smallfootprint building... jbk4001 Plumbing Pictures 33 01-18-2009 11:05 PM
Green building code grandpa Plumbing Code 5 10-13-2008 11:11 AM


All times are GMT -4. The time now is 04:11 PM.


Copyright 2000-2014 Escalate Media LP. All Rights Reserved
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | ElectricianTalk.com | HVACSite.com | PaintTalk.com | RoofingTalk.com

Search Engine Optimization by vBSEO 3.6.1