Default Leaky sharkbite

found my first leaking sharkbite the other day. It was a 1/2" coupling adapting copper to pex on a hot water line. The copper side was fine but the teeth in the sharkbite cut grooves in the outside wall of the pex allowing it to slide out and leak. I could tell from the grooves in the pex that it had been pushed in all the way and it did have the pex insert in it. The pex was straight and not under any strain. Must have been expansion/contraction the caused it to pull out.
ho said it was done about 2 years ago.. anyone else seen this happen?
it was Bow superpex
rzp 06 is online now   Reply With Quote

Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. PlumbingZone.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Old 04-11-2012, 08:06 AM   #2
Moderator
 
plbgbiz's Avatar
 
Join Date: Aug 2010
Posts: 15,596

View plbgbiz's Photo Album My Photos
Default

I have seen them leak on copper after about 6 months.
plbgbiz is online now   Reply With Quote
The Following User Says Thank You to plbgbiz For This Useful Post:
Protech (04-12-2012)
Old 04-11-2012, 08:40 AM   #3
hero
 
damnplumber's Avatar
 
Join Date: Jan 2012
Location: Joshua Tree, CA
Posts: 350

View damnplumber's Photo Album My Photos
Default

If the pipe was not deburred or chamfered, it could have scorred the sharkbite causing it to leak. Ask me how I know?
damnplumber is offline   Reply With Quote
The Following User Says Thank You to damnplumber For This Useful Post:
Tommy plumber (04-11-2012)
Old 04-11-2012, 10:11 AM   #4
Senior Member
 
Will's Avatar
 
Join Date: Jun 2010
Location: Newcastle, OK
Posts: 3,228

View Will's Photo Album My Photos
Default

I don't mind the O-ring seal, probably last a long, long, long time. What bothers me about the sharkbite type of fittings is that nothing keeps them rotating and the expansion and contraction can't be good for them. Seems like it would prematurely wear out the O-Ring seal. Not sure why anyone would use sharkbite on PEX anyway, not like it's hard to hook up PEX as it is. Even in tight spots.
__________________
Will Rogers Plumbing (405) 323-2852
Moore, Oklahoma
"We Unclog Drains That Others Can't!"
http://www.willrogersplumbing.com/
http://www.facebook.com/#!/pages/Will-Rogers-Plumbing/112198585505675
Will is offline   Reply With Quote
Old 04-11-2012, 10:52 AM   #5
Member
 
Join Date: Dec 2008
Location: Anaheim
Posts: 98

View wookie's Photo Album My Photos
Default

Have'nt seen them leak yet in the field but if theres going to be any movement of any type they will leak. Just have not run into them. Not a matter of IF but When they leak. Just like the very popular John Guest fittings. Fine when new but get some time on them and a little movement= leak.

I do use hackbites on temporary work.

wookie
wookie is offline   Reply With Quote
Old 04-11-2012, 10:59 AM   #6
Lego Expert
 
GREENPLUM's Avatar
 
Join Date: Jul 2008
Location: ...
Posts: 3,481

View GREENPLUM's Photo Album My Photos
Default

Quote:
Originally Posted by Will View Post
I Not sure why anyone would use sharkbite on PEX anyway, not like it's hard to hook up PEX as it is. Even in tight spots.

PEX or Copper to CPVC,

that would be a reason to use hackbites
GREENPLUM is offline   Reply With Quote
Old 04-11-2012, 11:14 AM   #7
Plumba
 
Qball415's Avatar
 
Join Date: Nov 2010
Posts: 1,442

View Qball415's Photo Album My Photos
Default

Quote:
Originally Posted by Will
I don't mind the O-ring seal, probably last a long, long, long time. What bothers me about the sharkbite type of fittings is that nothing keeps them rotating and the expansion and contraction can't be good for them. Seems like it would prematurely wear out the O-Ring seal. Not sure why anyone would use sharkbite on PEX anyway, not like it's hard to hook up PEX as it is. Even in tight spots.
If I did run into a situation where I ran into pex. I don't have an expander or crimping tools to do a pex repair and would either refer call out or worst case use a Sharkbite connector. I don't know another product to use as a transition.
Qball415 is offline   Reply With Quote
Old 04-11-2012, 11:49 AM   #8
Registered Member
 
Join Date: Feb 2011
Location: Washington State
Posts: 8,892

View Widdershins's Photo Album My Photos
Default

Quote:
Originally Posted by Qball415 View Post
If I did run into a situation where I ran into pex. I don't have an expander or crimping tools to do a pex repair and would either refer call out or worst case use a Sharkbite connector. I don't know another product to use as a transition.
Considering how pretty much all brands of PEX can be crimped, it might be worth your while to pick up a crimper one of these days.

As for sharkbites -- I'll use them to transition from copper to pex in a crawlspace or for a temporary connection, but I would never bury one inside of a wall or ceiling.
Widdershins is offline   Reply With Quote
Old 04-11-2012, 12:46 PM   #9
Moderator
 
Tommy plumber's Avatar
 
Join Date: Feb 2010
Location: Florida
Posts: 9,169

View Tommy plumber's Photo Album My Photos
Default

Quote:
Originally Posted by Widdershins View Post
Considering how pretty much all brands of PEX can be crimped, it might be worth your while to pick up a crimper one of these days.

As for sharkbites -- I'll use them to transition from copper to pex in a crawlspace or for a temporary connection, but I would never bury one inside of a wall or ceiling.







Agreed. They have their place.

I'll use them sometimes after I remove a W/H. I'll cap the (2) 3/4" lines while I run to go get the replacement W/H.
__________________
Hire a licensed master plumber.
Tommy plumber is offline   Reply With Quote
The Following User Says Thank You to Tommy plumber For This Useful Post:
Protech (04-12-2012)
Old 04-11-2012, 09:59 PM   #10
Senior Member
 
RealCraftsMan's Avatar
 
Join Date: Dec 2011
Location: Houston
Posts: 954

View RealCraftsMan's Photo Album My Photos
Default

They will fail, please keep using them. In a few years I will make the big bucks fixing all the hack work!
__________________
No sir that's really the price and no I will not take any off.
RealCraftsMan is offline   Reply With Quote
The Following 2 Users Say Thank You to RealCraftsMan For This Useful Post:
bizzybeeplumbin (04-12-2012), Protech (04-12-2012)
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
SharkBite DUNBAR PLUMBING General Plumbing Discussion 65 03-29-2012 12:32 AM
Leaky Wiki ckoch407 Off Topic 17 09-03-2011 08:41 AM
Caulking around leaky kitchen sink? della1 General Plumbing Discussion 3 06-24-2011 08:32 AM
Leaky shower valve Scott V General Plumbing Discussion 2 06-16-2009 10:13 AM
Leaky WH Airgap Plumbing Pictures 37 05-06-2009 03:25 AM


All times are GMT -4. The time now is 04:33 PM.


Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | ElectricianTalk.com | HVACSite.com | PaintTalk.com | RoofingTalk.com

Search Engine Optimization by vBSEO 3.6.1