OK, so I have a job that I am bidding. It's 2 tankless heaters with a recirc system.
The pump and my electronics are not allowed...rather approved for outdoor installations. I was thinking of some kind of enclosure with a hinged door with an open bottom. What suggestions do you have? Mounting the pump / electronics under the house is a last resort and I really do not want to do that. There is a 75 gal in a tin house on the side of the furthest exterior wall. There is no recirc as of now, and opposite end is taking about 4.5 minutes for HW. The design is correct I just need to protect my pump / housing. Leaving the tin house is not an option. Looking for economical way of doing this because the rest of the job is gonna cost a boat load. I don't want to price myself out of the job for some eloborate housing. Was thinking 3/4" treated ply with a back against the stuccoo wall so I don't have to flash it. Advice? Thanks! |
|
|
|
Join the #1 Plumbers Forum Today - It's Totally Free! PlumbingZone.com - Are you a Professional Plumbing Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for plumbers to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that PlumbingZone.com is a great community to join. Best of all it's totally free! |
|
|
#2 |
|
Senior Member
|
it may be kind of funkybut how about one of those smaller rubbermaid sheds? they make the real shallow ones that people install right on the side of their house, much like the tin doghouse that's already there. it'll look a little better i think and it's water proof. otherwise, i think you'd need to build something.
paul |
|
|
|
|
|
#4 |
|
Senior Member
|
How about mounting the pump in a cabinet at the far end of the loop? Put an aquastat on it and it will shut down when it's hot, negating the necessity of having to purge cold water from the return line. Of course, you may have noise issues in that cabinet, but at least it's inside.
|
|
|
|
|
|
#6 | |
|
Always Something
|
Quote:
|
|
|
|
|
|
|
#7 |
|
Senior Member
|
Other then the fact that your pump has to move at least .5 gpm (or in some cases .75 gpm) to fire the heater, how is this different? The pump would shut off when aquastat reaches set temp, thus shutting down the heater (if no hot water is being called for). However, you'd still have to account for the cold water sandwich when the pump is off and a hot tap turns on.
|
|
|
|
|
|
#8 |
|
Always Something
|
Nope. I do my recircs a little different. Grundfos Aquastats are crap and do nothing with respect to tankless. My system is different. I Could do the pump on the other end, but I want the whole line 3/4". My pump will do about 3.5 gpm. The energy saved at putting the stat down line is not worth the hassle to me and it's more work than it needs to be.
|
|
|
|
|
|
#9 |
|
Senior Member
|
ask HELGORE
__________________
www.paradiseplumbinganddrains.com ![]() ft. worth plumber . plumber dallas . keller plumber . plumber benbrook. plumber arlington |
|
|
|
![]() |
| Thread Tools | |
| Display Modes | |
|
|
Similar Threads
|
||||
| Thread | Thread Starter | Forum | Replies | Last Post |
| Outdoor gas fireplace | Tankless | General Plumbing Discussion | 3 | 02-21-2009 10:15 PM |